SAF OPAL Ethernet IP Interface MS6 SERIES Uživatelský manuál Strana 11

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 13
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 10
Opal Pro to SAF GlobalData
Page 11
Output Words
Name
Description
Word 1
Status
Bit 0 Ready to Run (drive is enable
and has 3 phase power)
Bit 1 Running (start is regulating)
Bit 2 Full On (starter is phased fully
on)
Bit 3 Up to Speed (started is
phased fully on and the current is
below 105% of nameplate current as
set in 13.01)
Bit 4 Reverse
Bit 5 Jogging
Bit 6 DC Injecting
Bit 7 Faulted
Bit 8 IOC Fault
Bit 9 MOL Fault
Bit 10 Phase Loss Fault
Bit 11 Shear Pin Fault
Bit 12 Shorted SCR Fault
Bit 13 Heat Sink OT Fault
Bit 14 Reserved
Bit 15 Watch Dog Bit
Word 2
Current
Feedback
833 = 500% of motor name plate
current as set in 13.01
Word 3
Phase
Angle
Actual
Amount of time phased on in
microseconds
Parameter
Name
Description
1.01 (Word 4)
Current
Current feedback in Amps
1.02 (Word 5)
L1 to L2
Voltage
Line 1 to Line 2 Voltage in Volts
1.03(Word 6)
L1 to L3
Voltage
Line 1 to Line 3 Voltage in Volts
1.04(Word 7)
L2 to L3
Voltage
Line 2 to Line 3 Voltage in Volts
1.05(Word 8)
DI Status
Digital input status
Bit 0 Start
Bit 1 Stop
Bit 2 Jog
Bit 3 Reverse
Bit 4 Reset